Pressure transmitter CB 6000

Item number: CB6000

Messbereich / Medientemperatur

starting from 249,00 €

Excluding 19% VAT. , Your order is free shipping.

There are variations of this item. Please select the variation you wish.


Pressure transmitter CB 6000

Features:

  • Measuring ranges 0...160 mbar up to 0...400 bar
  • Linearity error including hysteresis <+ 0.2 % f.s.
  • Piezoresistive measuring system
  • Internal diaphragm (type series CB60 . .)
  • Flush mounted diaphragm (type series CE61 . .)
  • Wetted parts of stainless steel; completely welded
  • Stainless steel housing as standard or field housing
  • Type of protection IP 65, IP 67 option
  • Output signal: 4...20 mA, 0...20 mA option
  • Process temperature up to 140 °C (short term, for sterilization)
  • Explosion protection: II 2G EEx ib IIC T6

Technical Data:

Case design
Designs
- field housing IP 65 or IP 67, with cable gland
- right-angle plug DIN 43650, IP 65,
- cable connection, IP 67
- locking plug M12, IP 65
case material
- stainless steel material no. 1.4404/1.4305
electronics encapsulated with silicone.
Inner chamber aeration for measuring ranges
< 16 bar over case thread or connection cable
(depending on design)

Process connection:
see page 2 and order code for variants.
Material-no.: 1.4404 for sleeve and diaphragm.
0-ring seal from NBR (type series CE6100)

Temperature ranges:
ambient temperature: -25...+70 °C
storage temperature: -40...+90 °C
process temperature:
- standard:
-10...+80 °C
- with temperature -10...+140 °C
decoupler
(short term, for sterilization)
compensated temperature range: 0...50 °C

System filling:
silicon oil

Measuring ranges/overrange limits see order details
intermediate measuring ranges upon request

Response time:
= 20 ms

Measuring accuracy:
linearity error incl. hysteresis: <+ 0.2 % f.s.
(<+ 0.3 % f.s. for measuring ranges = 0...60 bar)
fixed-point adjustment accuracy of adjustment: <± 0.2 % f.s.
temperature effect im compensated temperature range 0...50 °C:
- zero point < 0.2 %/10 K f.s.
- span < 0.2 %/10 K f.s.
other values upon request

Auxiliary energy supply:
standard design:
- nominal voltage 24 V DC
- function range 6...30 V DC
- max. allowable operating voltage 30 V DC

Supply voltage influence
= 0.01 % f.s. / V

Signal output:
4...20 mA, 2-wire circuitry or
0...20 mA, 3-wire circuitry

Current limitation in output signal:
max. output current approx. 30 mA

Adjusting range:
approx. ± 5 % f.s.
zero point and measuring span separately
adjustable

Burden:
2-wire circuitry
2-Leiterschaltung
standard design Ra= (KOhm)UB= operating voltage Ra= max. permissible burden resistance (incl. lead)

Burden influence
for 500 ohm burden change: = 0.1 % f.s.

Ex approval
CENELEC approval according to ATEX
explosion protection intrinsically safe
Government Testing Laboratories
(TÜV) 00 ATEX 1557 X
II2G EEx ib IIC T6
- U max < 30 V DC
- I max < 150 mA
- P max < 1 W
- Ci < 49 nF
- Li < 33 µH

Weights:
case with plug connector
approx. 200 g
field housing: + approx. 260 g
with temperature decoupler
+ approx. 50 g

Installation position:
any, standard: vertical

EMC test:
noise immunity according to EN 50082
section 2, version March 1995 issue for
industry
emitted interference according to EN
50081section 1, 1993 issue for residential
and industrial areas
Device emits no radiation of its own


Spannungsversorgung: 6 - 30 V DC
Elektr. Anschluss: Winkelstecker
Schutzart: IP 65
Umgebungstemperatur: -25 °C ... +70 °C
Ausgang: 4 - 20 mA
Anschluss: G 1/2
Messsystem: Piezoresistiv
Medientemperatur: -10 °C ... +80 °C, optional bis +140 °C (kurzzeitig zur Sterilisation)
Zulassung: II 2 G Ex ib IIC T6 (Option)
Material Gehäuse: Edelstahl
Material Anschluss: 1.4404